:: Volume 11, Issue 3 (5-2022) ::
ieijqp 2022, 11(3): 61-71 Back to browse issues page
Simulation and Analysis of Using Interline bridge‐type fault current limiter in High Voltage Substations for Reducing Short Circuit Current, Voltage Drop and Improve the Stability of Distribution Generation; Case Study: Substation in Special Economic Zone of AMIRABAD Port
Seyed esmaeel Naghibi1 , Mohammad Mirzaie * 1, Taghi Barforoushi1
1- Faculty of Electrical and Computer Engineering, Babol Noshirvani University of Technology, Babol, Iran
Abstract:   (779 Views)

Due to the expansion and development of the distribution networks and the use of distributed generators (DGs), the level of short-circuit current has increased significantly. Increasing the short circuit current level provides several challenges for network equipment.
 In this paper, the effects of using the inter-line fault current limiter (IFCL) to reduce the short-circuit current and improve the stability of DGs installed in the 230/63/20 kV AMIRABAD substation as a case study are investigated. It includes several output feeders for connecting loads and four DGs to a common coupling point 20 kV bus. In this substation, the connection of DGs to supply the power required by consumers, has increased the short-circuit current to a greater amount than the nominal capacity of the equipment. Also the occurrence of short-circuit in one of the feeders has led to voltage sag in the common bus and the instability of the generators. This has caused the exit of generators and sensitive loads connected to parallel feeders and finally reduce the reliability. IFCL consists of several rectifier bridge circuits and a common limiting resistor. It inserts the common limiting resistor in fault path for limiting the fault current level and consequently the voltage drop in the case of short circuit of the feeders. To prove the efficiency of the proposed structure for solving the problems of the studied network, the substation components in PSCAD / EMTDC software are simulated. The simulation results show that the proposed IFCL effectively reduces the fault current and voltage drop, as well as improves the stability of DGs.

Keywords: short circuit current, voltage sag, Interline bridge‐type fault current limiter, distributed generator
Full-Text [PDF 2140 kb]   (136 Downloads)    
Type of Study: Research |
Received: 2021/10/6 | Accepted: 2022/05/31 | Published: 2022/05/31
References
1. Chen, L. and etc. ( September 2022). Coordination of adaptive virtual resistance controller and flux-coupling-type fault current limiter for LVRT fulfillment of virtual synchronous generator, Electric Power Systems Research, 210, 108112. [DOI:10.1016/j.epsr.2022.108112]
2. CIGRE WG A3.10 (2003). Fault Current Limiters in High Electrical Medium and Voltage Systems, CIGRE Technical Brochure, no. 239.
3. Elshiekh,M., Elwakeel, A. and etc.( October 2021 ) . Utilising SMES-FCL to improve the transient behaviour of a doubly fed induction generator DC wind system. International Journal Electrical Power Energy System, 131, 107099. [DOI:10.1016/j.ijepes.2021.107099]
4. Firouzi, M., Gharehpetian, G. B. (June 2013 ) .Improving Fault Ride-Through Capability of Fixed-Speed Wind Turbine by Using Bridge-Type Fault Current Limiter, IEEE Transactions on Energy Conversion, 28(2), 361-369. [DOI:10.1109/TEC.2013.2248366]
5. Firouzi,M. (2018), A modified capacitive bridge-type fault current limiter (CBFCL) for LVRT performance enhancement of wind power plants,International Transactions on Electrical Energy Systems, 28(3), e2505. [DOI:10.1002/etep.2505]
6. Firouzi, M., Shafiee, M. R., Gharehpetian, G. B. (2020).Multi-Resistor Bridge-Type FCL for FRT Capability Improvement of DFIG-based Wind Farm, IET Energy System Integration,2(4),316-324. [DOI:10.1049/iet-esi.2020.0010]
7. Ghanbari, T., Farjah, E., Naseri, F. (October 2018).Power quality improvement of radial feeders using an efficient method, Electric Power Systems Research, 163, 140-153. [DOI:10.1016/j.epsr.2018.05.027]
8. Heydary, A., Radmanesh, H., Rouzbehi, K. , Mehrizi-Sani, A., Gharehpetian, G. B.( October 2020). Inductive fault current limiters: A review, Electric Power Systems Research, 187, 106499. [DOI:10.1016/j.epsr.2020.106499]
9. IEEE Std 551™ (2006). IEEE Recommended Practice for Calculating Short-Circuit Currents in Industrial and Commercial Power Systems, IEEE Violet Book.
10. Jager, J., et. Al.(2008). Interaction Between Fault Current Limiters and Protection-A Glance at the Final Report of CIGRE WG-A3.16, IEEE Power and Energy Society General Meeting - Conversion and Delivery of Electrical Energy in the 21st Century. [DOI:10.1109/PES.2008.4596464]
11. Javadi, H.( Mar. 2011).Fault Current Limiter using a Series Impedance Combined With Bus Sectionalizing Circuit Breaker, International Journal Electrical Power Energy System, 33(3), 731-736. [DOI:10.1016/j.ijepes.2010.11.023]
12. Kundor, P.(1994).Introduction to power system stability, Power System Dynamics Stability and Control, New York, McGraw Hill.
13. Naghibi, S. E., Mirzaie, M., Barforoshi, T.( May 2020 ). Interline bridge-type fault current limiter: A novel approach for limiting fault current in distribution network, International Transactions on Electrical Energy Systems, 30(5). e12326. [DOI:10.1002/2050-7038.12326]
14. Schmitt, H. (16 October 2006).Fault Current Limiters Report on the Activities of CIGRE WG A3.16, IEEE Power Engineering Society General Meeting, Montreal. [DOI:10.1109/PES.2006.1709205]
15. Shafiee, M. R., Kartijkolaie, H. Sh. , Firouzi, M., Mobayen, S., Fekih, A. (20 November 2020).Dynamic Multi-Cell FCL to Improve the Fault Ride through Capability of DFIG-Based Wind Farms, Energies, 13(22), 6071. [DOI:10.3390/en13226071]
16. Sousa, W. T. B., Kottonau, D. , Karrari, Sh., Geisbüsch, J., Noe, M. (January 2021).Deployment of a Resistive Superconducting Fault Current Limiter for Improvement of Voltage Quality and Transient Recovery Voltage, IEEE Transactions on Applied Superconductivity, 31(1). [DOI:10.1109/TASC.2020.3016460]
17. Thakur, P., Singh,A.K. (2013).A novel way to quantify the magnitude of voltage sag, Electrical Engineering, 95, 331-340. [DOI:10.1007/s00202-012-0268-0]
18. Yousefi, H., Mirzaie, M., Aminifar, F.( 2016 ) .Reliability Assessment of HV Substations Equipped with Fault Current Limiter Considering Changes of Failure Rate of Components, IET Generation, Transmission & Distribution, 10(7),1504 - 1509 . [DOI:10.1049/iet-gtd.2014.1250]
19. Zolfaghari, M., Gilvanejad, M., Gharehpetian, G. B.(2020).A survey on fault current limiters: Development and technical aspects, International Journal of Electrical Power & Energy Systems, 118, 105729. [DOI:10.1016/j.ijepes.2019.105729]
20. نقیبی، س. ا.، ملیجی، ف.، میرزایی، م.، بارفروشی، ت. (آبان 1397). جايابي بهينه محدودکننده جريان خطای مناسب شبکه برق منطقه¬ای مازندران و گلستان در سال 1403 به همراه مقايسه فنی و اقتصادی با روشهای مرسوم، سی و سومين کنفرانس بين¬المللي برق ایران، تهران.


XML   Persian Abstract   Print


Download citation:
BibTeX | RIS | EndNote | Medlars | ProCite | Reference Manager | RefWorks
Send citation to:

naghibi S E, mirzaie M, Barforoushi T. Simulation and Analysis of Using Interline bridge‐type fault current limiter in High Voltage Substations for Reducing Short Circuit Current, Voltage Drop and Improve the Stability of Distribution Generation; Case Study: Substation in Special Economic Zone of AMIRABAD Port. ieijqp 2022; 11 (3) :61-71
URL: http://ieijqp.ir/article-1-854-en.html


Rights and permissions
Creative Commons License This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.
Volume 11, Issue 3 (5-2022) Back to browse issues page
نشریه علمی- پژوهشی کیفیت و بهره وری صنعت برق ایران Iranian Electric Industry Journal of Quality and Productivity
Persian site map - English site map - Created in 0.06 seconds with 40 queries by YEKTAWEB 4645