:: Volume 11, Issue 1 (4-2022) ::
ieijqp 2022, 11(1): 82-96 Back to browse issues page
Detection of partial discharge in covered conductor medium voltage distribution lines
Mohammad Ali Yavari1 , Davoud Abootorabi Zarchi * 1, Alireza Sedighi Anaraki1
1- Department of Electrical Engineering, Yazd University, Yazd, Iran,
Abstract:   (2114 Views)
This paper presents a method for detecting the location of partial discharge in medium voltage covered conductor (CC) lines. The use of CCs is increasing day by day due to higher reliability, less susceptibility to climate change, and fewer short circuit faults than overhead lines.  CCs are commonly used in forests.  The lack of rapid failure detection of protection relays when the tree falls on the CC is one of its most important disadvantages. Scratching of CC insulation due to a tree falling on it usually leads to partial discharge (PD), which can lead to short circuit faults in the long run. Because the CC may be installed in an impassable path, it is difficult to detect a tree falling on the CC or the growing foliage colliding with the CC, and if not done promptly, it can lead to a short circuit fault. In this paper, for the first time, while obtaining a three-phase CC model, the falling of a tree on CC is simulated by applying a PD pulse source at the desired location. The proposed method is that first the PD signal is applied at the location of the electrical posts and the waveform obtained at the end of the line is stored and then their FFT is calculated as reference signals. To find the location of an unknown location PD, the signal obtained at the end of the line is saved after eliminating its main component of frequency and noise. Afterward, its FFT is calculated. Then, using the method of maximum correlation of signals, the nearest electric pole to the location of PD is determined. The proposed method was applied in different cases in a sample system, and satisfactory results were obtained.
Keywords: Covered Conductor, Partial Discharge, Location detection, Maximum Correlation Method, Phase to Ground Capacitor, Covered Conductor Modeling, EMTP.
Full-Text [PDF 1152 kb]   (530 Downloads)    
Type of Study: Research | Subject: Special
Received: 2021/08/5 | Accepted: 2021/12/26 | Published: 2022/04/14
References
1. Anderson P., (1995), Analysis of Faulted Power Systems, Jhon Wiley, IEEE book series.
2. Adhikari, N. (2021, March). Analysis of Partial Discharge Measurements on Medium Voltage Covered Conductor for Overhead Transmission Lines. In 2021 12th International Symposium on Advanced Topics in Electrical Engineering (ATEE) (pp. 1-5). IEEE. [DOI:10.1109/ATEE52255.2021.9425289]
3. Caliari, G. (2020). High voltage covered conductor overhead lines: detection of incipient tree faults.‏
4. Chen, K., Vantuch, T., Zhang, Y., Hu, J., & He, J. (2020). Fault Detection for Covered Conductors With High-Frequency Voltage Signals: From Local Patterns to Global Features. IEEE Transactions on Smart Grid, 12(2), 1602-1614.‏ [DOI:10.1109/TSG.2020.3032527]
5. Cheng, D. K. Field and Wave Electromagnetics: Pearson New International Edition. Pearson Education, Incorporated, 2013.‏
6. Dong, M., & Sun, J. (2020). Partial discharge detection on aerial covered conductors using time-series decomposition and long short-term memory network. Electric Power Systems Research, 184, 106318.‏ [DOI:10.1016/j.epsr.2020.106318]
7. El-Shaarawy, Z., Talaat, M., & El-Zein, A. (2021). Field reduction simulation based on covered conductors design in medium voltage lines. Results in Engineering, 10, 100217.‏ [DOI:10.1016/j.rineng.2021.100217]
8. Hashmi, G. M., Papazyan, R., & Lehtonen, M. (2007, April). Comparing wave propagation characteristics of MV XLPE cable and covered-conductor overhead line using time domain reflectometry technique. In 2007 International Conference on Electrical Engineering (pp. 1-6). IEEE.‏ [DOI:10.1109/ICEE.2007.4287345]
9. Hashmi, G. M. (2008). Partial discharge detection for condition monitoring of covered-conductor overhead distribution networks using Rogowski coil. Teknillinen korkeakoulu.‏ [DOI:10.1109/ICEE.2008.4553933]
10. Hashmi, M., Lehtonen, M., Nordman, M., Jabbar, R. A., & Qureshi, S. A. (2012). Wavelet-based de-noising of on-line PD Signals captured by Pearson coil in covered-conductor overhead distribution networks. International Journal of Electrical Power & Energy Systems, 43(1), 1185-1192.‏ [DOI:10.1016/j.ijepes.2012.06.035]
11. He, W., Li, H., Liang, D., Sun, H., Yang, C., Wei, J., & Yuan, Z. (2015). Implementation of a novel double-side technique for partial discharge detection and location in covered conductor overhead distribution networks. Measurement Science and Technology, 26(12), 125009.‏ [DOI:10.1088/0957-0233/26/12/125009]
12. Isa, M., Elkalashy, N. I., Hashmi, G. M., & Lehtonen, M. (2012). Experimental evaluation of Rogowski coil performance for locating PD in energized overhead covered-conductor feeder. Journal of Energy and Power Engineering, 6(6), 949-959.‏
13. Kiitam, I., Taklaja, P., & Tuttelberg, K. (2018, May). Voltage withstand properties of the insulation of different types of medium voltage covered overhead line conductors. In 2018 19th International Scientific Conference on Electric Power Engineering (EPE) (pp. 1-4). IEEE.‏ [DOI:10.1109/EPE.2018.8396011]
14. Kreuger F. H., "Discharge detection in high voltage equipment," 1989.
15. Li, H., Cui, X., Wang, H., Yan, Y., Lu, Y., & Zhao, K. (2020, December). A Novel Partial Discharge Locating System for 10-kV Covered Conductor Lines in Distribution Network. In 2020 10th International Conference on Power and Energy Systems (ICPES) (pp. 379-383). IEEE.‏ [DOI:10.1109/ICPES51309.2020.9349708]
16. Misák, S., Fulnecek, J., Vantuch, T., Buriánek, T., & Jezowicz, T. (2017). A complex classification approach of partial discharges from covered conductors in real environment. IEEE Transactions on Dielectrics and Electrical Insulation, 24(2), 1097-1104.‏ [DOI:10.1109/TDEI.2017.006135]
17. Pakonen, P. (2007). Detection of incipient tree faults on high voltage covered conductor lines. Tampere University of Technology.‏
18. Peng, X., Zhou, C., Hepburn, D. M., Judd, M. D., & Siew, W. H. (2013). Application of K-Means method to pattern recognition in on-line cable partial discharge monitoring. IEEE Transactions on Dielectrics and Electrical Insulation, 20(3), 754-761.‏. [DOI:10.1109/TDEI.2013.6518945]
19. Shafiq, M., Hussain, G. A., Kütt, L., & Lehtonen, M. (2014). Effect of geometrical parameters on high frequency performance of Rogowski coil for partial discharge measurements. Measurement, 49, 126-137.‏ [DOI:10.1016/j.measurement.2013.11.048]
20. Tleis, N. (2007). Power systems modelling and fault analysis: theory and practice. Elsevier.‏
21. www.emtp.com
22. شیفر، ا، اوپنهایم، ر، (1398)، پردازش سیگنال گسسته در زمان، چاپ پنجم، انتشارات نص، تهران.
23. کومار، آ، (1395) سیگنال‌ها و سیستم‌ها، چاپ اول ، انتشارات صفار، تهران.
24. نوبخت، ع؛ شمشیری، ه. (1397) راهنمای اجرای شبکه های هادی روکش‌دار؛ چاپ اول، انتشارات نوید شیراز, شیراز.


XML   Persian Abstract   Print


Download citation:
BibTeX | RIS | EndNote | Medlars | ProCite | Reference Manager | RefWorks
Send citation to:

Yavari M A, Abootorabi Zarchi D, Sedighi Anaraki A. Detection of partial discharge in covered conductor medium voltage distribution lines. ieijqp 2022; 11 (1) :82-96
URL: http://ieijqp.ir/article-1-836-en.html


Rights and permissions
Creative Commons License This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.
Volume 11, Issue 1 (4-2022) Back to browse issues page
نشریه علمی- پژوهشی کیفیت و بهره وری صنعت برق ایران Iranian Electric Industry Journal of Quality and Productivity
Persian site map - English site map - Created in 0.05 seconds with 40 queries by YEKTAWEB 4645