:: Volume 5, Issue 1 (7-2016) ::
ieijqp 2016, 5(1): 100-111 Back to browse issues page
A Novel Distance Relaying Algorithm for Series-Compensated Double-Circuit Transmission Lines for Cross-Country Faults to Consider the Effects of Grounding Impedance
Mohammad Paryad , Kazem Mazlumi * 1
Abstract:   (5433 Views)

In this paper, a novel algorithm is proposed to protect the first zone of distance relay in series-compensated double-circuit transmission lines for cross-country faults. Cross-country fault is considered as two single-phase faults that occurs in different phases and locations in double-circuit transmission lines. The relation between the sending end of the line current and the receiving end of the line current is obtained. The proposed algorithm using the one-end sampling data from line, determine different locations of two single-phase faults that occurs on the line. Performance of this method is studied for 300km long double-circuit transmission line compensated by series capacitor in both ends and in impedance grounded network using simulation in MATLAB / SIMULINK software.

Keywords: Double-Circuit Transmission Lines, Series-Compensation, series capacitor, Distance protection, Cross-Country Fault
Full-Text [PDF 1219 kb]   (2338 Downloads)    
Type of Study: Research | Subject: Special
Received: 2015/07/28 | Accepted: 2015/12/21 | Published: 2016/08/15


XML   Persian Abstract   Print



Rights and permissions
Creative Commons License This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.
Volume 5, Issue 1 (7-2016) Back to browse issues page